Home » Industrial Flexible & Special Cable Products » Type 441 Semiconductive Screened Cable (AS/NZS 2802) | 1.1/1.1 kV Class 2 & 3.3–22 kV Class 1 Reeling & Trailing Mining Cable

Type 441 Semiconductive Screened Cable (AS/NZS 2802) | 1.1/1.1 kV Class 2 & 3.3–22 kV Class 1 Reeling & Trailing Mining Cable

AS/NZS 2802 Type 441 semiconductive elastomer screened flexible mining cable covering both Type 441.1 Class 2 (1.1/1.1 kV, 6–300 mm²) for general mine trailing and Type 441 Class 1 (3.3 kV to 22 kV, 25–300 mm²) with reduced radial walls for smaller diameter and lower weight on materials-handling reels, stacker-reclaimers, and mobile mining machinery.

Standard & Dual Radial Series
AS/NZS 2802 Class 2 (1.1 kV) & Class 1 (3.3–22 kV)
Cross-Section Coverage
6–300 mm² (51 Standard Sizes Total)
Core, Earth & Pilot Layout
3 Screened Phases + 3 Earths + 1 Central Pilot
Non-Metallic Flex Screen
Extruded Semiconductive Elastomer (Zero Wire Fatigue)
Reinforced Sheath
Polyaramid / Open-Weave Braid + XHD-85-PCP
Operating Temp & Flame
−25 °C to +90 °C | C1 Flame Retardant
Datasheets: Class 2 (1.1 kV) & Class 1 (3.3–22 kV)

Application & Operating Conditions

AS/NZS 2802 Type 441 is a semiconductive elastomer screened flexible mining cable family (1.1 kV to 22 kV, 6–300 mm²) built with three phase cores, three interstitial earth cores, and one central extensible pilot — supplied in Type 441.1 Class 2 (1.1/1.1 kV) for heavy general mining trailing and Type 441 Class 1 (3.3 kV to 22 kV) for materials handling, slow reeling, and compact-diameter trailing equipment.

Non-Metallic Screen Flex Life

Replacing copper wire core braids with extruded semiconductive elastomer screens and three interstitial earth cores eliminates broken-wire insulation puncture under cyclic bending.

Compact Class 1 MV Reeling (3.3–22 kV)

Class 1 XR-EP-90 insulation and XHD-85-PCP sheath radials significantly reduce overall diameter and weight compared with Class 2 cables (e.g., 106 mm vs. 115 mm at 22 kV 95 mm²) for bulk-handling reels.

Hard-Rock & Open-Cut 1.1 kV Trailing

Type 441.1 Class 2 (1.1/1.1 kV, 4.2 kV test) powers jumbo drills, LHDs, mobile crushers, and pumps in open-cut and underground metalliferous mines.

Underground Coal Mine Application? AS/NZS 2802 cables apply to surface mines, ports, and non-coal underground mines. For underground coal mining semiconductive-screened cables (1.1–11 kV), view AS/NZS 1802 Type 241.

Cable Construction (Type 441.1 Class 2 & Type 441 Class 1)

Both Type 441 series share a symmetrical 3-phase + 3-interstitial-earth + 1-central-pilot architecture enclosed within a semiconductive cradle/bedding and braid-reinforced heavy-duty elastomer outer sheath.

Layer / ComponentMaterial & AS/NZS 2802 Specification
1. Phase ConductorsMultiple-stranded circular flexible tinned annealed copper wire, rope lay (AS/NZS 1125-2.10; 6–300 mm²)
2. EPR InsulationClass 2 R-EP-90 on 1.1 kV Type 441.1 (1.5–3.0 mm); Class 1 XR-EP-90 on 3.3–22 kV Type 441 (2.2–7.6 mm)
3. Semiconductive ScreenExtruded black semiconductive elastomer screen over each phase core with core identification, laid over a semiconductive cradle
4. Three Interstitial EarthsThree semiconductive/elastomer-covered tinned copper earth cores in continuous contact with the semiconductive core screens (2.2–50.8 mm² each)
5. Central Extensible PilotOne EPR-covered central extensible pilot (max DC resistance 3 Ω/100m up to 35 mm²; 2 Ω/100m above 35 mm²)
6. Braid-Reinforced SheathOpen-weave / polyaramid reinforcement braid under extra-heavy-duty black XHD-85-PCP / AS/NZS 3808 elastomer sheath
Type 441.1 Class 2 1.1 kV cross-section diagram 441.1 Class 2 (1.1 kV)
Type 441 Class 1 3.3-22 kV cross-section diagram 441 Class 1 (3.3–22 kV)

Dual Cross-Section Comparison: Both grades maintain 3 phases + 3 earths + 1 central pilot inside a braid-reinforced sheath.

Technical Characteristics

Engineered to AS/NZS 2802 for +90 °C continuous operation, C1 flame retardancy, and water/oil immersion resilience across surface mining and bulk materials-handling plants.

ParameterAS/NZS 2802 Rated Value
Manufacturing StandardAS/NZS 2802 (Conductor: AS/NZS 1125-2.10 | Elastomers: AS/NZS 3808)
Low-Voltage Class 2 SeriesType 441.1 Class 2 — 1.1/1.1 kV (4.2 kV AC Test), 6–300 mm² (13 sizes)
Medium-Voltage Class 1 SeriesType 441.3 (3.3 kV), 441.6 (6.6 kV), 441.11 (11 kV), 441.22 (22 kV) — 25–300 mm² (38 sizes)
Central Pilot DC ResistanceMax. 3.0 Ω/100m (≤35 mm² phase size) | Max. 2.0 Ω/100m (>35 mm² phase size)
Operating Temperature Range−25 °C min. installation to +90 °C max. continuous conductor temperature
Immersion & Flame RatingExcellent water/oil immersion performance, high flex life, C1 flame retardant

Specification Tables (51 Standard Sizes: 1.1 kV Class 2 & 3.3–22 kV Class 1)

Expand any voltage grade below to inspect full dimensional, stranding, electrical impedance, earth sizing, and mass parameters.

Type 441.1 Class 2 — Rated Voltage: 1.1/1.1 kV (6 mm² to 300 mm² | 13 Sizes)
Area (mm²)Phase StrandCond. Dia. (mm)Insul. Wall / Dia. (mm)Earth StrandEarth Area (mm²)Pilot StrandSheath (mm)Overall Dia. (mm)Copper Mass (kg/km)Cable Mass (kg/km)
3 × 684 / 0.303.41.5 / 6.530 / 0.302.224 / 0.203.828.52441100
3 × 1077 / 0.404.61.5 / 7.748 / 0.303.424 / 0.203.831.13941350
3 × 16126 / 0.405.71.6 / 9.075 / 0.305.324 / 0.203.934.16211750
3 × 25209 / 0.407.21.6 / 10.575 / 0.305.324 / 0.204.237.98852300
3 × 35285 / 0.408.51.6 / 11.875 / 0.305.324 / 0.204.441.211732750
3 × 50380 / 0.4010.01.7 / 13.5114 / 0.308.140 / 0.204.945.916863500
3 × 70203 / 0.6712.01.8 / 16.036 / 0.6712.740 / 0.205.352.223944800
3 × 95259 / 0.6713.22.0 / 17.645 / 0.6715.940 / 0.205.856.732065800
3 × 120336 / 0.6715.32.1 / 20.057 / 0.6720.140 / 0.206.362.740477250
3 × 150427 / 0.6717.12.3 / 22.277 / 0.6727.240 / 0.206.768.351168800
3 × 185518 / 0.6719.22.5 / 24.791 / 0.6732.140 / 0.207.374.9626510500
3 × 240672 / 0.6721.82.8 / 27.9112 / 0.6739.540 / 0.208.083.3806213300
3 × 300854 / 0.6724.43.0 / 30.9144 / 0.6750.840 / 0.208.791.21011616300
Type 441.3 Class 1 — Rated Voltage: 3.3/3.3 kV (25 mm² to 300 mm² | 10 Sizes)
Area (mm²)Cond. Dia. (mm)Insul. (mm)AC Res. (Ω/km)React. (Ω/km)Volt Drop (mV/A·m)Cap. (μF/km)Earth Each (mm²)Sheath (mm)Cable Dia. (mm)Mass (kg/100m)
3 × 257.22.20.9510.1201.660.3955.34.945.9320
3 × 358.42.20.6980.1151.230.4375.35.248.8370
3 × 509.72.40.5230.1130.9270.45085.754.4470
3 × 7012.02.40.3460.1050.6260.52512.56.059.5595
3 × 9513.32.40.2710.1000.5000.563166.362.7685
3 × 12015.32.40.2100.09590.4000.628206.567.2815
3 × 15017.22.40.1660.09290.3290.687276.671.3965
3 × 18518.82.40.1370.09060.2840.741326.775.11105
3 × 24021.72.40.1070.08740.2390.83339.56.981.61350
3 × 30024.32.40.08510.08500.2080.917507.087.41620
Type 441.6 Class 1 — Rated Voltage: 6.6/6.6 kV (25 mm² to 300 mm² | 10 Sizes)
Area (mm²)Cond. Dia. (mm)Insul. (mm)AC Res. (Ω/km)React. (Ω/km)Volt Drop (mV/A·m)Cap. (μF/km)Earth Each (mm²)Sheath (mm)Cable Dia. (mm)Mass (kg/100m)
3 × 257.23.00.9510.1261.660.3095.35.350.2370
3 × 358.43.00.6980.1211.230.3405.35.653.3425
3 × 509.73.00.5230.1160.9280.37586.057.6515
3 × 7012.03.00.3460.1080.6280.43512.56.362.6640
3 × 9513.33.00.2710.1030.5020.465166.465.5725
3 × 12015.33.00.2100.09900.4020.518206.670.1860
3 × 15017.23.00.1660.09580.3320.566276.774.21015
3 × 18518.83.00.1370.09340.2870.608326.878.01155
3 × 24021.73.00.1060.08990.2410.68239.57.084.61410
3 × 30024.33.00.08490.08770.2110.754507.190.41680
Type 441.11 Class 1 — Rated Voltage: 11/11 kV (25 mm² to 300 mm² | 10 Sizes)
Area (mm²)Cond. Dia. (mm)Insul. (mm)AC Res. (Ω/km)React. (Ω/km)Volt Drop (mV/A·m)Cap. (μF/km)Earth Each (mm²)Sheath (mm)Cable Dia. (mm)Mass (kg/100m)
3 × 257.25.00.9510.1371.660.2175.36.360.9500
3 × 358.45.00.6980.1311.230.2365.36.463.6555
3 × 509.75.00.5230.1240.9310.25886.566.7635
3 × 7012.05.00.3460.1160.6320.29612.56.671.6765
3 × 9513.35.00.2710.1120.5080.317166.874.8870
3 × 12015.35.00.2100.1080.4090.350206.979.31010
3 × 15017.25.00.1660.1040.3390.381277.083.61180
3 × 18518.85.00.1370.1010.2950.407327.187.21320
3 × 24021.75.00.1060.09700.2490.45339.57.393.81585
3 × 30024.35.00.08460.09420.2190.499507.5100.01880
Type 441.22 Class 1 — Rated Voltage: 22/22 kV (35 mm² to 240 mm² | 8 Sizes)
Area (mm²)Cond. Dia. (mm)Insul. (mm)AC Res. (Ω/km)React. (Ω/km)Volt Drop (mV/A·m)Cap. (μF/km)Earth Each (mm²)Sheath (mm)Cable Dia. (mm)Mass (kg/100m)
3 × 358.47.60.6980.1431.230.1785.36.976.0750
3 × 509.77.60.5230.1360.9360.19487.079.2840
3 × 7012.07.60.3460.1270.6380.21912.57.184.1980
3 × 9513.37.60.2710.1230.5150.234167.287.01085
3 × 12015.37.60.2100.1180.4170.256207.391.71245
3 × 15017.27.60.1650.1130.3460.276277.495.81415
3 × 18518.87.60.1360.1100.3030.294327.699.81580
3 × 24021.77.60.1060.1050.2580.32539.57.71061850

Selection: Type 441 vs. Type 455 vs. Type 409

Comparing AS/NZS 2802 semiconductive and composite screened cables ensures compatibility with existing coupler pinouts and reeling drum bend radii.

Cable ModelEarth / Pilot Geometry & Target Service
Type 441 (This Product)Semiconductive screen + 3 interstitial earths + 1 central pilot (1.1 kV Class 2 & 3.3–22 kV Class 1, up to 300 mm²). Symmetrical 3-earth balance with compact Class 1 MV OD.
Type 455 (Class 1 Reeling)Type 455 also uses semiconductive core screens (3.3–11 kV) but places 2 earths + 1 larger pilot in the three outer interstices (no central pilot) for slow reeling drums.
Type 409 (Class 2 Trailing)For severe rock-drag open-cut trailing requiring heavy Class 2 walls at 3.3–22 kV and metallic composite braids, specify Type 409.

Frequently Asked Questions (FAQ)

Technical answers on Class 1 vs. Class 2 radial walls, 22 kV cross-section range, and pilot resistance.

Why does Type 441 use Class 2 at 1.1 kV (Type 441.1) and Class 1 at 3.3–22 kV?

At 1.1/1.1 kV (Type 441.1 Class 2), thicker mechanical walls protect trailing cables dragged directly behind jumbos and LHDs. At 3.3 kV to 22 kV (Type 441 Class 1), high-grade XR-EP-90 insulation allows thinner dielectric radials (e.g., 2.2–2.4 mm at 3.3 kV, 5.0 mm at 11 kV, 7.6 mm at 22 kV) to reduce cable OD and drum torque on stackers, reclaimers, and mobile substations.

Does Type 441.22 cover large 22 kV cross-sections up to 240 mm²?

Yes. Unlike Class 2 22 kV cables that top out at 95 mm² due to outer diameter limits, Type 441.22 Class 1 spans 8 standard sizes from 35 mm² all the way to 240 mm² (106 mm nominal OD) for high-MVA 22 kV bulk materials handling and mine equipment.

Can TEBAOFLEX supply both official PDF datasheets with factory quotation packages?

Yes — both the Type 441.1 Class 2 (1.1 kV) Datasheet and the Type 441 Class 1 (3.3–22 kV) Datasheet are directly downloadable on this page.

Request a Quote for AS/NZS 2802 Type 441 Semiconductive Mining Cables

Specify Type 441.1 Class 2 (1.1 kV) or Type 441 Class 1 (3.3–22 kV), cross-section (6–300 mm²), and required drum lengths.

Explore All Mining & Tunneling Cables
Product Model

Type 441.1 Class 2 (1.1 kV) & Type 441 Class 1 (441.3, 441.6, 441.11, 441.22)

Standard

AS/NZS 2802

Voltage Rating

1.1/1.1 kV (Class 2), 3.3/3.3 kV, 6.6/6.6 kV, 11/11 kV, 22/22 kV (Class 1)

Nominal Conductor Area

6–300 mm² (1.1 kV), 25–300 mm² (3.3–11 kV), 35–240 mm² (22 kV)

Conductor Material

Flexible rope-lay tinned annealed copper (3 phase + 3 interstitial earths + 1 central pilot)

Insulation & Screen

R-EP-90 (Class 2, 1.1 kV) / XR-EP-90 (Class 1, 3.3–22 kV) EPR + semiconductive elastomer screen

Interstitial Earth Cores

3 semiconductive/elastomer-covered tinned copper earth cores (2.2–50.8 mm² each)

Central Pilot Core

1 EPR-covered central extensible pilot (max DC res. 3 Ω/100m <=35 mm²; 2 Ω/100m >35 mm²)

Outer Sheath & Reinforcement

Open-weave / polyaramid braid under heavy-duty XHD-85-PCP / elastomer outer sheath

Operating Temperature & Flame

−25 °C min. installation to +90 °C max. continuous conductor, C1 flame performance