Home » Industrial Cable Guides, Case Studies & Technical Insights » RG7H1R / RG7OZR Cable Applications: Select by Installation Route

RG7H1R / RG7OZR Cable Applications: Select by Installation Route

RG7H1R / RG7OZR Cable Applications Overview

RG7H1R and RG7OZR cables are medium voltage EPR-insulated power cables used for MV power distribution, airport lighting systems, and industrial plant power. The unarmoured RG7H1R is ideal for indoor tray and conduit installations, while the armoured RG7OZR provides mechanical protection for direct burial and outdoor applications.

View our RG7H1R airport lighting cable and RG7OZR armoured MV cable product pages for specifications.

RG7H1OR EPR medium voltage power cable by TEBAOFLEX showing EPR insulation construction
RG7H1OR EPR medium voltage power cable — the standard for MV distribution and airport lighting applications

Airport Runway Lighting Systems

RG7H1R cable is specifically designed for airport runway and taxiway lighting:

  • Primary series lighting: MV cable powering constant current regulators for runway edge lights
  • Approach lighting: Power supply to approach lighting systems and precision approach path indicators
  • Taxiway lighting: MV distribution to taxiway centerline and edge lights
  • Apron lighting: Power supply to apron floodlighting systems
  • Buried installation: RG7H1R cables are buried alongside runways in ducts or direct-laid

The 3.6/6kV rating is standard for airport series lighting circuits per FAA and ICAO requirements.

RG7H1R cable route in a typical airport runway lighting circuit
RG7H1R in airport lighting: the EPR insulation and 3.6/6kV rating are specifically designed for airport series lighting circuits

Substation and Switchgear MV Distribution

RG7OZR armoured cable is used for substation power distribution:

  • MV switchgear feeders: Armoured cable connections from MV switchgear to transformers
  • Substation auxiliary power: MV power supply to substation auxiliary systems
  • Transformer feeders: MV cable from switchgear to MV/LV transformers
  • Ring main units: MV cable connections between ring main units
  • Cable termination: Heat shrink or cold shrink termination kits at switchgear and transformer connections
RG7OZR armoured MV cable in substation and industrial power distribution showing cable termination and underground duct installation
RG7OZR in substation: steel wire armour provides mechanical protection for underground and direct burial installations between switchgear and transformers

Industrial Plant MV Distribution

RG7OZR is widely used in industrial facilities:

  • Plant MV distribution: Power supply from substation to industrial process areas
  • Motor power: MV power supply to large induction and synchronous motors
  • Underground duct banks: MV cable in concrete-encased duct banks for industrial sites
  • Direct burial: Steel wire armour allows direct burial without additional conduit
  • Process equipment: MV power to large compressors, pumps, and fans
RG7OZR armoured MV cable industrial plant power distribution showing underground duct bank and direct burial installation from substation
RG7OZR in industrial plants: direct burial capability with steel wire armour eliminates the need for separate conduit, reducing installation cost

Application Selection Matrix

ApplicationRecommended CableTypical VoltageKey Requirement
Airport runway lightingRG7H1R3.6/6kVEPR insulation, buried
Substation MV feedersRG7OZR6/10-12/20kVSWA, direct burial
Industrial MV distributionRG7OZR6/10-8.7/15kVSWA, underground duct
Indoor cable tray (MV)RG7H1R3.6/6-8.7/15kVNo armour needed
MV motor powerRG7OZR3.6/6-6/10kVSWA, mechanical protection

Installation Best Practices

  • Bending radius: Minimum 12× OD (single-core), 15× OD (3-core)
  • Terminations: Use heat shrink or cold shrink MV termination kits — never use LV methods
  • Armour bonding: Ground armour at both ends for RG7OZR — use armour glands with bonding
  • Screen grounding: Bond copper wire screen at both ends for fault current path
  • Joints: Use MV cable joint kits rated for same voltage — maintain insulation and screen continuity
  • Duct installation: Pulling tension per manufacturer’s specification, use cable pulling compound
  • Direct burial: Minimum burial depth 0.6m (industrial), 0.8m (public areas); use warning tape above cable

Why Choose TEBAOFLEX for RG7H1R / RG7OZR Cable?

  • IEC 60502-2 compliant manufacturing
  • EPR insulation rated 90°C for continuous operation
  • Both unarmoured and armoured versions available
  • Wide voltage range: 3.6/6kV to 12/20kV
  • Complete type test support
  • Global MV project experience

Contact TEBAOFLEX for RG7H1R / RG7OZR cable selection and project pricing.

Project Verification Before Selection

This applications page should be used as a starting point for engineering review, not as proof of a direct substitute. RG7H1R and RG7OZR must be checked against the approved project requirement and selected product documentation. Verify voltage, conductor size, core arrangement, insulation and outer protection, route, mechanical exposure, termination and required marking.

For medium-voltage and offshore applications, the cable name alone cannot establish suitability. The installation route, environmental exposure, armour or mechanical-protection requirement and project approval documents determine which construction should be evaluated.

Verification itemWhy it mattersEvidence to request
Electrical configurationConfirms voltage, conductor and core arrangement.Project specification and selected datasheet.
Installation routeDefines mechanical and environmental duty.Route drawing, installation method and site conditions.
Protection requirementSupports review of armour, sheath and routing safeguards.Mechanical-risk assessment and project documents.
Required marking or approvalEnsures project acceptance is reviewed correctly.Approved purchase specification and compliance documents.

Common Mistakes

Do not treat product names, standards from unrelated documents or broad application labels as automatic evidence of equivalence. Do not select by conductor size alone. Each proposed cable must be reviewed for the actual route, equipment duty and required documentation.

RFQ Checklist

Send the application, voltage, conductor size, core count, route, movement if applicable, environment, required standards, existing cable marking, termination details and quantity. TEBAOFLEX CABLE can review the supplied requirements and recommend a suitable construction.

FAQ

Can these cable types be directly substituted?

Not automatically. Confirm the complete construction, route and project acceptance requirements before substitution.

What should be provided for a technical review?

Provide the datasheet or existing marking together with the equipment and installation details.