Home » Industrial Flexible & Special Cable Products » SANS 1520-2 Type 611 & Type 611-ECC Mining Cable | 6.35/11kV Dragline & Reeling Cable

SANS 1520-2 Type 611 & Type 611-ECC Mining Cable | 6.35/11kV Dragline & Reeling Cable

SANS 1520-2 Type 611 and Type 611-ECC 6.35/11 kV screened reeling and section feeder cables (25 mm² to 240 mm²) engineered for open-cast draglines, electric mining shovels, overburden drills, and movable 11 kV pit substations. Features triple-extruded EPR insulation with strippable semi-conducting core screens, composite nylon/tinned-copper phase braids, 16-string open nylon anti-torsion reinforcement, and heavy-duty black CR polychloroprene sheaths in both 3-pilot (Type 611) and bare-earth (Type 611-ECC) variants.

Standard
SANS 1520-2; SANS 1411-1; SANS 1411-3
Rated Voltage
6.35 / 11 kV AC
Dielectric System
Triple-Extruded EPR + Strippable Semi-Con Screen
Size & Ampacity Range
25–240 mm² (105 A to 400 A @ 30 °C)
Operating Temp. & Bend
-25 °C to +90 °C | Min. 9 × OD
1s Fault Capacity
Up to 29.3 kA Phase | Up to 17.0 kA ECC
Engineering Datasheet: Download Verified SANS 1520-2 Type 611 / 611-ECC PDF (3 Pages):

Application & Operating Conditions

SANS 1520-2 Type 611 and Type 611-ECC are 6.35/11 kV medium-voltage flexible screened reeling, trailing, and section feeder cables manufactured to SANS 1520-2 for powering open-cast walking draglines, electric rope shovels, hydraulic excavators, blast-hole drills, and hazardous-area underground or surface mobile substations.

11 kV Draglines, Shovels & Reeling

Reinforced with a minimum 16-string open nylon braid vulcanized between double CR sheaths to handle 1.1 kN to 10.8 kN dynamic reeling and pit-bench trailing loads.

Triple-Extruded Strippable Core Screen

Co-extruded conductor screen, 6.35/11 kV EPR insulation, and free-stripping semi-conducting outer core screen prevent partial discharge under bending and speed field termination.

Dual Earth-Fault Topologies (611 / 611-ECC)

Choose Type 611 (3 EPM pilots; 1.6–4.1 kA screen fault rating) for NER-limited 11 kV systems, or Type 611-ECC (2 EPM pilots + 16–120 mm² bare ECC; up to 17.0 kA) for high-fault feeders.

Minimum Bending Radius (9 × Overall Diameter): For 6.35/11 kV Type 611 and Type 611-ECC cables (OD 50.7 mm to 85.6 mm), maintain a minimum drum barrel and sheave bending radius of 9 × OD (456 mm at 25 mm² up to 770 mm at 240 mm²) to preserve partial-discharge-free triple-extruded screen bonding.

Cable Construction (SANS 1520-2 Type 611 & Type 611-ECC)

Engineered to SANS 1520-2, SANS 1411-1, and SANS 1411-3 for void-free 11 kV electrical field control combined with heavy elastomeric mechanical protection.

Layer / ComponentMaterial & SANS 1520-2 Engineering Specification
1. Power ConductorsClass 5 flexible stranded tinned annealed copper to SANS 1411-1 (25 mm² to 240 mm²).
2. Triple-Extruded 11 kV InsulationThermosetting EPR dielectric compound (SANS 1411-3) triple-extruded with semi-conducting conductor screen and a strippable semi-conducting core screen.
3. Composite Phase ScreensIndividual nylon and 0.31 mm tinned copper wire composite braid (29 mm² to 52 mm² screen cross-section) incorporating Red, Yellow, and Blue phase tracers.
4. Interstitial EPM Pilot CoresEPM-insulated flexible tinned copper pilot cores (10–25 mm²): three pilots in Type 611; two pilots in Type 611-ECC.
5. Bare ECC Variant ConductorType 611-ECC only: one interstitial pilot replaced by an uninsulated stranded tinned copper ECC conductor (16 mm² to 120 mm²; 0.15–0.7 Ω/km min. ECC resistance).
6. Inner Sheath & Nylon BraidCR polychloroprene rubber inner sheath + open nylon reinforcement braid (minimum 16 strings).
7. Outer SheathHeavy-duty black CR polychloroprene rubber outer sheath — UV resistant, sunlight resistant, oil resistant, and abrasion/flame resistant.
Cross-section diagram of SANS 1520-2 Type 611 & Type 611-ECC Dragline & Reeling Cable 6.35/11kV

SANS 1520-2 Type 611 & Type 611-ECC (25–240 mm²): 3 triple-extruded 6.35/11 kV EPR power cores with strippable semi-conducting screens and composite copper/nylon braids, laid with 3 EPM pilots (Type 611) or 2 EPM pilots + 1 bare tinned copper ECC (Type 611-ECC).

Triple-Extruded 11kV EPR + Composite Screens + ECC Heavy-Duty Black Polychloroprene (CR) Inner & Outer Sheath

Technical Characteristics

Complete electrical, thermal, and mechanical operating ratings for SANS 1520-2 Type 611 and Type 611-ECC 6.35/11 kV mining cables.

ParameterSANS 1520-2 Rated Value
Applicable StandardsSANS 1520-2; SANS 1411-1; SANS 1411-3
Rated Voltage (Uo/U)6.35 / 11 kV AC
Operating Temperature Range-25 °C to +90 °C
Minimum Bending Radius9 × Overall Cable Diameter (456 mm at 25 mm² to 770 mm at 240 mm²)
Ambient Current Rating Basis105 A (25 mm²) to 400 A (240 mm²) at 30 °C Ambient
Maximum Pulling Tension1.1 kN (25 mm²) up to 10.8 kN (240 mm²)
1-Second Conductor S/C Rating3.1 kA (25 mm²) up to 29.3 kA (240 mm²)
1-Second Screen / ECC S/C RatingScreen S/C: 1.6–4.1 kA | ECC S/C (Type 611-ECC): 3.6–17.0 kA

SANS 1520-2 Type 611 & Type 611-ECC Complete Specification Tables (25–240 mm²)

Nominal dimensional, ECC conductor, standardized mass (kg/km), impedance, current rating, and 1-second short-circuit withstand tables across all nine 6.35/11 kV sizes.

1. SANS 1520-2 Type 611 (Standard 3-Pilot) — Dimensions, Screen Area, Tension & Nominal Weight (9 Sizes)
Configuration (mm²)Power Wire Dia. (mm)Power Cond. Dia. (mm)Screen Wire Dia. (mm)Screen Area (mm²)Pilot Size (mm²)Pilot Wire / Cond. Dia. (mm)Max. Tension (kN)Overall Dia. (mm)Nominal Weight (kg/km)
Type 611 3×25 + 3×100.416.80.3129100.41 / 4.21.150.74,100
Type 611 3×35 + 3×100.418.50.3131100.41 / 4.21.652.24,500
Type 611 3×50 + 3×100.4110.30.3134100.41 / 4.22.359.45,300
Type 611 3×70 + 3×160.5111.90.3137160.41 / 5.33.260.46,500
Type 611 3×95 + 3×160.5113.50.3141160.41 / 5.34.365.28,000
Type 611 3×120 + 3×160.5115.50.3143160.41 / 5.35.471.39,800
Type 611 3×150 + 3×250.5117.30.3146250.41 / 6.86.875.010,700
Type 611 3×185 + 3×250.5120.20.3149250.41 / 6.88.385.113,400
Type 611 3×240 + 3×250.5122.90.3152250.41 / 6.810.885.614,700
2. SANS 1520-2 Type 611-ECC (2 Pilots + 1 Bare ECC) — ECC Sizing & Nominal Weight (9 Sizes)
Configuration (mm²)Conductor Size (mm²)Interstitial Pilots (mm²)Bare ECC Size (mm²)ECC Max. Wire Dia. (mm)Overall Dia. (mm)Max. Tension (kN)Nominal Weight (kg/km)
Type 611-ECC 3×25 + 2×10 + 16ECC252 × 10160.4150.71.14,200
Type 611-ECC 3×35 + 2×10 + 25ECC352 × 10250.4152.21.64,600
Type 611-ECC 3×50 + 2×10 + 25ECC502 × 10250.4159.42.35,400
Type 611-ECC 3×70 + 2×16 + 35ECC702 × 16350.4160.43.26,700
Type 611-ECC 3×95 + 2×16 + 50ECC952 × 16500.4165.24.38,200
Type 611-ECC 3×120 + 2×16 + 70ECC1202 × 16700.5171.35.410,200
Type 611-ECC 3×150 + 2×25 + 95ECC1502 × 25950.5175.06.810,900
Type 611-ECC 3×185 + 2×25 + 95ECC1852 × 25950.5185.18.313,900
Type 611-ECC 3×240 + 2×25 + 120ECC2402 × 251200.5185.610.815,000
3. SANS 1520-2 Type 611 & 611-ECC — Electrical Resistance, Impedance, Current & 1s Short-Circuit Ratings
Conductor Size (mm²)DC Res. 20 °C (Ω/km)DC Res. 90 °C (Ω/km)Reactance (Ω/km)Impedance 90 °C (Ω/km)Min. Screen Res. (Ω/km)Min. ECC Res. (Ω/km)Current @ 30 °C (A)Cond. S/C 1s (kA)Screen S/C 1s (kA)ECC S/C 1s (kA)
25 mm²0.7951.050.1341.061.60.71053.11.63.6
35 mm²0.5650.7490.1240.7591.20.51304.32.15.0
50 mm²0.3930.5210.1170.5340.80.51606.13.15.0
70 mm²0.2770.3680.1130.3850.70.41958.53.57.5
95 mm²0.2100.2790.1080.2990.60.323011.64.19.0
120 mm²0.1640.2180.1030.2410.60.2326014.64.111.5
150 mm²0.1320.1760.0980.2010.60.1830018.34.114.0
185 mm²0.1080.1450.0960.1740.60.1834022.574.114.0
240 mm²0.08170.1100.0920.1430.60.1540029.34.117.0
Mass Unit Standardization Note: Nominal weights in Tables 1 and 2 are expressed in true kg/km (4,100–15,000 kg/km, equivalent to 410–1,500 kg/100m) for exact dragline reel and freight calculations.

SANS 1520-1 & SANS 1520-2 South African Mining Cable Selection Matrix

Compare Type 611 & Type 611-ECC (6.35/11 kV) across the full SANS 1520 low-voltage and medium-voltage mining trailing and reeling cable family.

SANS 1520 ModelVoltage, Core & Pilot Architecture & Primary Mining Duty
SANS 1520-1 Type 41 (640/1100V)SANS 1520-1 Type 41 (640/1100V): 640/1100 V 4-core (3 composite-screened power cores + 1 unscreened pilot, 2.5–25 mm²) CR-sheathed reeling & trailing cable for drills, pumps, and portable underground tools.
SANS 1520-1 Type 61A (640/1100V TPU)SANS 1520-1 Type 61A (640/1100V TPU): 640/1100 V heavy-duty 6-core (3 composite-screened power cores + 3 interstitial pilots) reeling & trailing cable with abrasion-resistant TPU outer sheath (black or reflective transparent).
SANS 1520-1 Type 61B (0.64/1.1kV)SANS 1520-1 Type 61B (0.64/1.1kV): 0.64/1.1 kV 6-core (35–150 mm²) non-reeling coalface cable with triple-extruded RD 3 EPR, 80% tinned copper braid screens, 3 interstitial pilots, and RS 6 CR sheaths.
SANS 1520-2 Type 63 (1.9/3.3kV)SANS 1520-2 Type 63 (1.9/3.3kV): 1.9/3.3 kV medium-voltage 6-core (25–240 mm², up to 520 A) composite-screened reeling & trailing cable for 3.3 kV continuous miners, shearers, and jumbo drills.
SANS 1520-2 Type 66 & 66-ECC (3.8/6.6kV)SANS 1520-2 Type 66 & 66-ECC (3.8/6.6kV): 3.8/6.6 kV screened reeling & section feeder cable (25–240 mm²) with 3 interstitial pilots (Type 66) or 2 pilots + 1 bare ECC earth conductor up to 17.0 kA 1s (Type 66-ECC).
SANS 1520-2 Type 611 & 611-ECC (6.35/11kV) (This Product)6.35/11 kV medium-voltage dragline, shovel, and reeling cable (25–240 mm²) with triple-extruded EPR insulation, strippable semi-con screen, and CR outer sheath.
SANS 1520-2 Type 622 & 622-ECC (12.7/22kV)SANS 1520-2 Type 622 & 622-ECC (12.7/22kV): 12.7/22 kV heavy-duty open-cast dragline, excavator, and mobile pit substation feeder cable (25–150 mm²) in 3-pilot or high-fault ECC topology.
SANS 1520-2 Type 633 & 633-ECC (19/33kV)SANS 1520-2 Type 633 & 633-ECC (19/33kV): 19/33 kV highest-voltage SANS 1520-2 screened reeling & pit feeder cable (25–120 mm²) delivering up to ~14.8 MVA three-phase bench capacity.

Frequently Asked Questions (FAQ)

Technical FAQs for 11 kV open-cast dragline, shovel, and section feeder engineers specifying SANS 1520-2 Type 611 / 611-ECC.

Why does SANS 1520-2 Type 611 specify a strippable semi-conducting core screen?

At 6.35/11 kV, radial electrical field gradients require a smooth, void-free interface between the EPR dielectric and the metallic braid screen to prevent corona and partial discharge. Triple-extruding a controlled-adhesion strippable semi-conducting screen guarantees zero air pockets during reeling while allowing jointers to peel the screen cleanly without scoring the 11 kV EPR insulation.

When should I specify Type 611-ECC instead of standard Type 611 on an 11 kV mine network?

Specify Type 611 when your 11 kV pit substation uses neutral-earthing resistors (NERs) limiting earth-fault current below 1.6–4.1 kA and requires three insulated pilot cores. Specify Type 611-ECC when feeding mobile substations, draglines, or shovels with prospective earth-fault currents up to 3.6–17.0 kA (1s) where a dedicated bare tinned copper earth conductor is required.

How does SANS 1520-2 Type 611 compare with Australian AS/NZS 2802 Type 411 (6.35/11 kV)?

Both serve 6.35/11 kV draglines, shovels, and reeling drums, but follow different regional coupler and earth-pilot standards: SANS 1520-2 Type 611 uses composite tinned-copper/nylon braided phase screens plus three interstitial EPM pilots (or 2 pilots + 1 bare ECC) and an open 16-string nylon sheath reinforcement braid tailored to Southern African mine protection relays.

What routine high-voltage factory tests are performed on TEBAOFLEX Type 611 cables?

Every drum undergoes conductor DC resistance measurement, partial discharge testing, high-voltage AC withstand testing per SANS 1520-2, semi-conducting screen strip-force verification, and dimensional/sheath inspection prior to export dispatch.

Request a Quote for SANS 1520-2 Type 611 or Type 611-ECC (6.35/11 kV)

Send your required variant (Type 611 or Type 611-ECC), cross-section (25–240 mm²), and drum cut lengths for direct factory pricing and test certification.

Explore All Mining & Tunneling Cables
Standard

SANS 1520-2; SANS 1411-1; SANS 1411-3

Cable Type

Type 611 & Type 611-ECC 11kV Screened Dragline, Shovel & Reeling Cable

Voltage Rating

6.35/11kV

Core Configuration

Type 611: 3 Power + 3 EPM Pilots, Type 611-ECC: 3 Power + 2 Pilots + 1 Bare ECC

Cross-Section Range

25 mm² to 240 mm² (9 Standard Sizes per Variant)

Conductor Material

Class 5 Flexible Stranded Tinned Annealed Copper

Insulation & Screen

Triple-Extruded 11kV EPR + Strippable Semi-Con + Composite Copper/Nylon Braid

Sheath Material

CR Inner Sheath + 16-String Open Nylon Braid + Heavy-Duty Black CR Outer Sheath