Home » Industrial Flexible & Special Cable Products » YnKGY-żo 0.6/1 kV PVC Mining Power Cable | Polish Standard Yellow Flame-Retardant 3–5 Core Cable

YnKGY-żo 0.6/1 kV PVC Mining Power Cable | Polish Standard Yellow Flame-Retardant 3–5 Core Cable

YnKGY-żo 0.6/1 kV is a lightweight, single-sheathed Polish standard (PN-G / PN-EN) fixed-installation mining power and lighting cable featuring Class 1 solid (1.5–6 mm²) or Class 2 stranded (10 mm²) bare copper conductors, a dedicated green-yellow (-żo) protective core, and a yellow OI > 29 PVC jacket.

Standard & InstallationPolish PN-G / PN-EN | Fixed Roadway & Plant WiringRated & Test Voltage0.6/1 kV | 3.5 kV AC Routine Test Voltage
Conductor Construction1.5–6 mm² Class 1 Solid | 10 mm² Class 2 Stranded CuCore Counts & PE (-żo)3, 4 & 5 Cores (with Green-Yellow PE Conductor)
Sheath ArchitectureSingle-Wall Yellow Flame-Retardant PVC (OI > 29)Temp. & Bend Radius-30°C to +70°C (-5°C Install) | 10 × OD Min. Bend
Engineering Datasheet: Full 15-size (3/4/5 × 1.5–10 mm²) dimensional & electrical scheduleDownload PDF Datasheet View 15 Sizes ↓
SKU: YNKGY-ZO-061KV Category: Brand:

Application & Underground Mining Service

YnKGY-żo 0.6/1 kV is a Polish PN-G and PN-EN compliant single-sheathed flame-retardant PVC power cable engineered for fixed electrical sub-distribution, permanent roadway lighting strings, and control-cabinet interconnections across non-explosion-hazard underground mine headings, open-pit excavations, and methane-free coal-dust class A galleries.

Permanent Roadway Lighting & Sub-Circuits

Compact 10.2–19.6 mm outer diameters and light 153–790 kg/km mass simplify overhead messenger-wire suspension, tray routing, and luminaire daisy-chaining along main haulage tunnels and shaft stations.

Dedicated Green-Yellow (-żo) Earth Core

Polish suffix -żo (zielono-żółty) designates a continuous green-yellow insulated protective earth conductor across all 3-core, 4-core, and 5-core variants for direct TN-S / IT switchgear termination.

Self-Extinguishing OI > 29 Yellow PVC

Special non-flammable yellow PVC outer jacket resists moisture, dilute mine acids, and bundled vertical flame spread to PN-EN 60332-1 and PN-EN 60332-3-24 without halogen-free cost penalties.

Mechanical Impact Upgrade: YnKGY-żo uses a single-wall yellow outer sheath for protected cable trays, brackets, and lighting strings. Where fixed cables face dripping shaft water or heavy mechanical abrasion without metallic armour, specify double-sheathed YKGYyn-żo 0.6/1 kV.

Cable Construction & Single-Sheath Anatomy

Following Polish fixed mining power cable nomenclature (Yn = flame-retardant PVC OI > 29, K = fixed power cable, G = mining duty, Y = PVC insulation, -żo = green-yellow earth), YnKGY-żo omits an inner sheath to deliver a slim, fast-stripping profile.

Layer / ComponentMaterial & Polish PN-G / PN-EN Standard Engineering Specification
1. ConductorsAnnealed bare copper conductors to PN-EN 60228: Class 1 solid single-wire for 1.5, 2.5, 4, and 6 mm²; Class 2 multi-wire stranded copper for 10 mm²*.
2. Core InsulationSpecial mining-grade polyvinyl chloride (PVC) dielectric rated for 0.6/1 kV continuous service and 3.5 kV AC routine withstand testing.
3. Core Color Identification3-core: Natural, Red, Green-Yellow; 4-core: Natural, Red, Blue, Green-Yellow; 5-core: Natural, Red, Blue, Black, Green-Yellow (-żo).
4. Core StrandingThree, four, or five insulated cores helically twisted together with compact lay pitch.
5. Outer SheathExtruded single-wall Yellow special non-flammable PVC outer sheath (Oxygen Index OI > 29) filling core interstices and passing PN-EN 60332-1 & PN-EN 60332-3-24.
YnKGY-żo 0.6/1 kV single-sheathed PVC mining power cable cross-section diagram showing 5 Class 1/2 bare copper cores with green-yellow PE inside a yellow OI above 29 PVC outer sheath

YnKGY-żo 0.6/1 kV Cross-Section (5-Core): Five PN-EN 60228 Class 1/2 bare copper conductors insulated with Special PVC (Natural, Red, Blue, Black, and Green-Yellow -żo protective core) enclosed directly inside a single-wall yellow flame-retardant PVC outer sheath (OI > 29).

Single-Wall Yellow Non-Flammable PVC Sheath (OI > 29) Green-Yellow (-żo) Protective Earth Core

Technical Characteristics

YnKGY-żo 0.6/1 kV provides a higher 3.5 kV AC routine dielectric test voltage than flexible trailing cords, verified 20°C DC conductor resistance (1.83–12.1 Ω/km), 1-second short-circuit thermal ratings (0.17–1.15 kA up to +160°C), and -30°C to +70°C static operating stability.

ParameterPolish PN-G / PN-EN Standard Rated Value
Cable Type DesignationYnKGY-żo 0.6/1 kV (Single-Sheathed Fixed Mining Power Cable with Green-Yellow PE)
Rated Voltage (Uo/U)0.6/1 kV (600/1000 V AC)
Routine AC Test Voltage3.5 kV (50 Hz)
Conductor Class (PN-EN 60228)Class 1 solid bare copper (1.5–6 mm²) | Class 2 stranded bare copper (10 mm²*)
Operating & Installation Temp.-30°C to +70°C operating | Min. -5°C cable temperature during installation without preheating
Max. Short-Circuit Temperature+160°C (1-second short-circuit ratings 0.17 kA to 1.15 kA)
Minimum Bending Radius10 × Overall Cable Diameter
Flame Retardancy & Oxygen IndexOxygen Index OI > 29; compliant with PN-EN 60332-1 and PN-EN 60332-3-24 (IEC 60332-3)
Permissible Mine ZonesFixed installations in non-explosion-hazard underground/open-pit mines, including methane-free workings classified as coal-dust hazard class A

Dimensional, Weight & Electrical Specifications (3, 4 & 5 Cores)

The two engineering tables below present verified nominal outer diameters (10.2–19.6 mm), single-sheath cable weights (153–790 kg/km), maximum 20°C DC conductor resistance, 50 Hz inductive reactance, current-carrying capacities (19–62 A), and 1-second short-circuit currents across all 15 standard YnKGY-żo sizes.

Table 1 — YnKGY-żo Dimensional & Weight Schedule (3, 4 & 5 Cores × 1.5–10 mm²)
Number & Cross-Section of Conductors (mm²)Conductor Class (PN-EN 60228)Core Color Code (incl. -żo PE)Approx. Outer Diameter (mm)Approx. Cable Weight (kg/km)
3×1.5Class 1 SolidNat / Red / G-Y10.2153
4×1.5Class 1 SolidNat / Red / Blu / G-Y11.1180
5×1.5Class 1 SolidNat / Red / Blu / Blk / G-Y11.8215
3×2.5Class 1 SolidNat / Red / G-Y11.0195
4×2.5Class 1 SolidNat / Red / Blu / G-Y12.0235
5×2.5Class 1 SolidNat / Red / Blu / Blk / G-Y12.9280
3×4Class 1 SolidNat / Red / G-Y12.9280
4×4Class 1 SolidNat / Red / Blu / G-Y14.2345
5×4Class 1 SolidNat / Red / Blu / Blk / G-Y15.2410
3×6Class 1 SolidNat / Red / G-Y13.9355
4×6Class 1 SolidNat / Red / Blu / G-Y15.4440
5×6Class 1 SolidNat / Red / Blu / Blk / G-Y16.6525
3×10*Class 2 StrandedNat / Red / G-Y16.4520
4×10*Class 2 StrandedNat / Red / Blu / G-Y18.1655
5×10*Class 2 StrandedNat / Red / Blu / Blk / G-Y19.6790
Table 2 — YnKGY-żo Electrical & Short-Circuit Ratings (1.5–10 mm²)
Conductor Cross-Section (mm²)Max. Conductor Resistance at 20°C (Ω/km)Phase Inductivity (mH/km)Inductive Reactance at 50 Hz (Ω/km)Current-Carrying Capacity (A)1s Short-Circuit Current (kA)
1.512.10.340.107190.17
2.57.410.320.099270.29
44.610.320.100370.46
63.080.300.095470.69
10*1.830.280.089621.15
*Stranded Conductor Note: Sizes marked with an asterisk (3x10*, 4x10*, 5x10*) utilize multi-wire Class 2 stranded copper conductors; 1.5–6 mm² sizes use Class 1 solid copper conductors.

Fixed Low-Voltage Polish Mining Cable Comparison

Compare lightweight single-sheathed YnKGY-żo against heavy double-sheathed YKGYyn-żo, round steel-wire armoured YKGYFoyn 0.6/1 kV, and flexible Class 5 YnOGY to select the exact mechanical radial protection and conductor flexibility required by your underground roadway bracket, cable tray, or vertical shaft route.

Polish PN-G Cable TypeSheath / Armour Construction, Size Scope & Fixed vs Mobile Duty
YnKGY-żo (0.6/1 kV — This Cable)Single-wall yellow OI > 29 PVC outer sheath (no inner sheath); Class 1/2 Cu, 3–5 cores × 1.5–10 mm²; lightweight fixed wiring for lighting strings, trays, and control rooms.
YKGYyn-żo (0.6/1 kV)Double-sheathed (extruded PVC inner sheath + yellow OI > 29 PVC outer sheath); identical 3–5 × 1.5–10 mm² electrical schedule with +3.7 mm radial wall armor against rough gallery walls and moisture.
YKGYFoyn 0.6/1 kVRound galvanized steel wire armoured (Fo / SWA) + yellow OI > 29 PVC outer sheath (3×10/6 to 3×120/35 mm²) for vertical shafts and steep inclines up to 90°.
YnOGY (0.6/1 kV)Flexible Class 5 copper (2.5–120 mm²) for movable or vibrating underground equipment where solid Class 1 conductors would fatigue.

Frequently Asked Questions (FAQ)

Review practical engineering answers to common technical specification, drum handling, and installation questions from Polish Upper Silesian and Czech Ostrava-Karvina mine electrical contractors regarding single-sheathed YnKGY-żo versus double-sheathed YKGYyn-żo radial wall thickness, cold-weather -5°C laying precautions, and methane-free coal-dust class A admissibility.

What is the structural difference between YnKGY-żo and YKGYyn-żo?

Both share identical Class 1/2 copper conductors, core colors, and electrical ratings. YnKGY-żo has a single yellow flame-retardant PVC outer sheath for lighter weight and smaller gland diameters, whereas YKGYyn-żo adds a dedicated extruded PVC inner sheath beneath the yellow outer jacket for tougher mechanical and moisture protection.

Can YnKGY-żo be installed in coal-dust zones?

YnKGY-żo is permitted in non-explosion-hazard underground and open-pit workings, including underground rooms and galleries classified as coal-dust explosion hazard class A provided no methane hazard is present.

What precaution applies when installing YnKGY-żo during winter surface-to-shaft transport?

Once installed statically, YnKGY-żo operates down to -30°C. However, during uncoiling, pulling, and bending on brackets, cable core temperature must be at least -5°C (preheat drums in a warm store if stored outdoors in sub-zero weather) to prevent PVC jacket cracking.

Can TEBAOFLEX supply YnKGY-żo without the green-yellow core (YnKGY) if needed?

Yes. While -żo (with green-yellow PE) is the standard stock configuration for 3-, 4-, and 5-core circuits, custom core color codes for IT ungrounded control circuits can be manufactured upon request.

Need YnKGY-żo 0.6/1 kV Fixed Roadway & Lighting Power Cable?

Send your bill of quantities across 3×1.5 mm² through 5×10* mm² to receive drum weights, gland sizing data, and direct factory export pricing.

Explore All Mining & Tunneling Cables
Product Model

YnKGY-żo

Standard

Polish PN-G Mining Standard, PN-EN 60228 Class 1 & 2, PN-EN 60332-3-24

Voltage Rating

0.6/1 kV (3.5 kV AC Routine Test)

Core & Size Range

3, 4 & 5 Cores × 1.5, 2.5, 4, 6 & 10 mm² (with -żo Green-Yellow PE)

Conductor Material

Bare Copper: Class 1 Solid (1.5–6 mm²) / Class 2 Stranded (10 mm²)

Insulation Material

Special Mining-Grade PVC

Sheath Material

Single-Wall Yellow Non-Flammable PVC Outer Sheath (OI > 29)

Operating Temperature

-30°C to +70°C (Min. Installation Temp. -5°C)

Application

Fixed Power & Roadway Lighting in Non-Methane Underground & Open-Pit Mines