Type P 2kV Armored Single Conductor Marine Power Cable is a single-conductor power cable for marine, offshore and oilfield installations that need mechanical protection and moisture-resistant construction. The documented design combines flexible tinned copper, irradiated XLPO insulation, metallic braid armor and a heavy-duty CSPE Type CP sheath.
Applications
Use this cable for power distribution on marine vessels, fixed or floating offshore facilities, and oilfield equipment. Final selection must match the installation route, operating voltage, environmental exposure and project requirements.
Construction Summary
| Component | Documented construction |
|---|---|
| Conductor | Flexible soft-annealed tinned copper |
| Insulation | Irradiated cross-linked polyolefin (XLPO) |
| Armor | Metallic braid armor; material selected to project requirement |
| Binder | Non-hygroscopic, non-wicking binder tape |
| Outer sheath | Heavy-duty chlorosulfonated polyethylene (CSPE), Type CP |
| Maximum conductor temperature | 125°C (source design data) |
| Typical applications | Marine, offshore and oilfield power systems |
Representative Dimensions and Ampacity
The values below are representative source data at 45°C ambient in free air or raceway. Confirm allowable current for the actual installation method, ambient temperature and applicable project rules.
| Conductor size | Approx. conductor area | Approx. overall diameter | Approx. weight | Ampacity at 100°C |
|---|---|---|---|---|
| 8 AWG | 7.6 mm² | 11.2 mm | 258 kg/km | 72 A |
| 4 AWG | 21 mm² | 14.8 mm | 493 kg/km | 128 A |
| 1/0 AWG | 56 mm² | 19.6 mm | 979 kg/km | 227 A |
| 4/0 AWG | 113 mm² | 24.2 mm | 1633 kg/km | 351 A |
| 444 kcmil | 227 mm² | 31.4 mm | 2973 kg/km | 588 A |
| 1111 kcmil | 562 mm² | 45.5 mm | 6491 kg/km | 1025 A |
Specification Guidance
The source documentation lists design references including 46 CFR Parts 110 and 111; API RP-14F/FZ; IEEE 45.8; IEC 61892-4; IEC 60092-350, IEC 60092-353 and IEC 60092-360. Verify the selected configuration, armor material, sheath colour, standards and approval requirements before ordering.
Request a Configuration
Share the voltage, conductor size, installation route and environmental conditions with TEBAOFLEX for configuration support.