RG7H1R vs RG7OZR Cable: MV EPR Cable Comparison

RG7H1R vs RG7OZR: What’s the Difference?

Both RG7H1R and RG7OZR are medium voltage EPR-insulated cables manufactured to IEC 60502-2, sharing the same conductor, insulation, and screen construction. The key difference: RG7H1R is unarmoured (copper wire screen only) for indoor tray and conduit installations, while RG7OZR is steel wire armoured for direct burial and outdoor mechanical protection.

TEBAOFLEX manufactures both types. View RG7H1R product page and RG7OZR product page for specifications.

RG7H1OR EPR medium voltage power cable by TEBAOFLEX
RG7H1R (unarmoured) and RG7OZR (armoured) — same EPR insulation, different armour configuration for different installation environments

Designation Breakdown

ElementRG7H1RRG7OZR
REPR insulationEPR insulation
G7MV rated voltage seriesMV rated voltage series
H1Standard construction
R vs OZRR = Unarmoured (PVC sheath)OZR = Steel wire armoured + PVC
ArmourNoneSteel wire armour (SWA)
InstallationIndoor, tray, conduitDirect burial, duct, outdoor
RG7H1R vs RG7OZR cable material comparison showing unarmoured vs armoured construction with steel wire armour protection level
Construction comparison: RG7H1R has copper wire screen only — RG7OZR adds steel wire armour over the screen for mechanical protection

Performance Comparison

PropertyRG7H1RRG7OZRAdvantage
Voltage rating3.6/6-12/20kV3.6/6-12/20kVTie
InsulationEPREPRTie
ConductorCopper Class 2Copper Class 2Tie
Metallic screenCopper wireCopper wireTie
Mechanical protectionScreen onlyScreen + SWARG7OZR
Direct burialNot recommendedYes (SWA)RG7OZR
WeightLowerHigher (armour)RG7H1R
Bending radius12× OD12× ODTie
CostLower~15-25% higherRG7H1R
Installation flexibilityEasier (lighter)More complex (armour bonding)RG7H1R
RG7H1R vs RG7OZR cable application comparison for airport lighting indoor substation vs outdoor underground direct burial
Application scenarios: RG7H1R for airport lighting and indoor substation (left) vs RG7OZR for outdoor underground and direct burial (right)

When to Choose RG7H1R (Unarmoured)

  • Airport runway lighting: 3.6/6kV series lighting cable buried in ducts or protective covers
  • Indoor cable tray: MV distribution within substations and switchgear rooms
  • Conduit installation: MV cable installed in conduits where mechanical protection is provided by conduit
  • Lighter weight required: Where cable support capacity is limited
  • Cost optimization: 15-25% less expensive than RG7OZR
  • Easier installation: No armour bonding or grounding required

When to Choose RG7OZR (Armoured)

  • Direct burial: Steel wire armour provides mechanical protection without conduit
  • Underground ducts: MV cable in underground duct banks
  • Outdoor installation: UV and weather resistant PVC sheath for outdoor environments
  • Industrial plant: MV distribution requiring rodent and impact protection
  • Substation feeders: MV cable from switchgear to transformer in buried runs
  • Mandatory mechanical protection: Where regulations require armour for buried MV cables
RG7H1R vs RG7OZR technical specification comparison table showing voltage armour type bending radius and application differences
Specification comparison: same voltage and insulation — the choice comes down to mechanical protection and installation environment

Cost Comparison

RG7OZR costs 15-25% more than RG7H1R due to:

  • Steel wire armour material and manufacturing process
  • Additional PVC bedding layer between screen and armour
  • Larger overall diameter (more PVC sheath material)

Best practice: Use RG7H1R for indoor and protected installations, RG7OZR for direct burial and outdoor. This optimizes cost while meeting all mechanical protection requirements.

Can RG7H1R and RG7OZR Be Interchanged?

RG7OZR can replace RG7H1R — it has all RG7H1R properties plus armour. But adds unnecessary cost and weight where armour isn’t required.

RG7H1R cannot replace RG7OZR — without armour, RG7H1R cannot be direct buried or used where mechanical protection is required. Substituting would violate installation regulations.

Summary: Which Cable Should You Choose?

If your installation is…Recommended cable
Airport runway lighting (buried in duct)RG7H1R
Indoor cable tray (substation)RG7H1R
Conduit installationRG7H1R
Direct burial (outdoor)RG7OZR (mandatory)
Underground duct bankRG7OZR
Substation to transformer (buried)RG7OZR

Contact TEBAOFLEX engineering for expert MV cable selection and competitive pricing.